700_Spannungsprüfer_Voltmeter

  • IEC 61243-3
  • VDE 0682 part 401
  • Voltage class B (AC 1000 V / DC 1000 V)
  • Overvoltage category: CAT IV 500 V, CAT III 1000 V
  • Protection class: IP 65 (dustproof / water jets protect)
    6 – first index: Protection against access to dangerous parts and protection
    against solid impurities, dustproof
    5 – second index: Protected against splashing water. Can also be used in wet weather.
  • Nominal voltage range (Voltage class A): 12 V to 690 V AC / 750 V DC
  • Internal resistance, measuring circuit: 220 kΩ
  • Internal resistance, load circuit – both push buttons actuated!:
    approx. 3,5 kΩ .. (25 kΩ)
  • Current consumption, measuring circuit: max. In 3.5 mA (690 V/ 750 V DC)
  • Current consumption, load circuit – both push buttons actuated!: approx. 0,25 A (690 V AC/ 750 V DC)
  • Polarity indication: LED +; LED – (indication handle = positive polarity) Indicating steps LED: 12 V+*; 12 V-*; 24 V+; 24 V-; 50 V; 120 V; 230 V; 400 V; 500 V; 690 V
    (*:with both push buttons actuated)
  • continuous indication by means of level indicator: 230 V – 690 V AC/ 750 V DC
  • max. indicating errors: Un ± 15 %, ELV Un – 15 %
  • Nominal frequency range f: 0 up to 60 Hz, Phase and phase sequence indication 50/60 Hz
  • Phase and phase-sequence indication: ≥ Un 230 V
  • Vibrating motor, starting: ≥ Un 230 V
  • max. permissible operating time ED: permissible up to 500 V ED = 30 s,
    permissible up to 750 V ED = 10 s, 240 s pause
  • Dimension: 250 mm, weight: approx. 190 g
  • Connecting cable length: approx. 900 mm
  • Operating and storing temperature range: -10 °C up to + 55 °C (climate category N)
  • Relative air humidity: 20 % up to 96 % (climate category N)
  • Return control times (thermal protection for vibration motor):
    Where the voltage exceeds 500 V max. 750 V the permissible temperature
    range max. ED=10s. Voltage / Time:
    230 V / 30 s
    400 V / 9 s
    750 V / 2 s
weight / gNorm
210 vde-gs