702_Duspol Digital_Duspol Digital

  • Two-pole voltage tester VDE GS
  • Tested and approved according to internationally valid standard IEC 61243-3 (DIN VDE 0682-401)
  • CAT IV 600 V or CAT III 1000 V
  • Protection class: IP 65 (dust-proof / water-resistant)
    6 – first index: Protection against access to dangerous parts and protection against solid impurities, dustproof
    5 – second index: Protected against splashing water. Can also be used in wet weather.
  • Nominal voltage range: 6 V up to AC 690 V/ DC 750 V
  • Internal resistance, measuring circuit: PTC 15 kΩ ≥ 360 kΩ
  • Internal resistance, load circuit – both push buttons actuated!: approx. 3.7 kΩ (150 kΩ)
  • Current consumption, measuring circuit: ma. < 3.5 mA AC/DC
  • Current consumption, load circuit – both push buttons actuated!: Ix 0.2A (750 V)
  • Polarity indication: LCD symbol +/-
  • Voltage indication, continuous 6 – 750 V
  • Voltage range I: up to approx. 80.0 V (88.8)
  • Voltage range II from approx. 80 V (888) onwards
  • max. indicating errors: ± 2 % of Voltage range, 20 – 150 Hz sinusoidal or DC, ELV Un – 15 %
  • Nominal frequency range f: 0 up to 150 Hz
  • Phase and phase-sequence indication: ≥ Un 230 V, 50/60 Hz
  • Vibrating motor, starting: ≥ Un 230 V
  • Test current, continuity check: max. 2 µA
  • Testing range, conducting resistance: 0 – 200 kΩ
  • Sound level acoustic signal: 55 dB
  • max. permissible operating time: ED = 30 s (max. 30 seconds), 240 s pause
  • HOLD function (AC ≤ 250 V, DC ≤ 250 V, DC ≤ 750 V), activation press button ≥ 1.5 s
  • Device switch-on at measuring voltage: ≥ 6 V
  • Connecting cable length: approx. 900 mm
  • Operating and storing temperature range: - 10 ° C up to + 55 ° C (climate category N)
  • Relative air humidity: 230 % up to 96 % (climate category N)
  • Battery: 2 x micro, LR03/ AAA (3 V)
  • Reverse control times (thermal protection):
    Voltage / Time:
    230 V / 30 s
    400 V / 9 s
    750 V / 2 s

ATTENTION: The voltage tester cannot be operated with the batteries being empty! Voltage checking without battery is possible upwards of a voltage of ≥ 50 V. Remove the batteries from the device at a longer storage!

weight / gNorm
300 vde-gs